| Communications: |
Dual port, fiber optic NFPA style 7 partyline, 9000¹ feet range minimum
Uses ST connectors |
| Inputs: |
4 or 8 zones - field selected networks allow choice of NO or NC contacts - relays, FACP contact outputs, security points |
| Mechanical: |
4.8" x 5.2" PC board - not including AC PS/battery charger
Mount within FACP - red or tan
11.375" x 11.375" x 3.5" in wall mounting enclosure
An enclosure that holds 6 units is available |
| End-of-Line resistor types: |
| Single resistor: |
Keltron network - H (fire applications) complies with UL style A |
| Dual resistor: |
Keltron network A (2 alarm level applications) complies with UL style A |
| 3 resistor: |
Keltron network D or E for 5 state reporting |
| Status LEDs (field enabled for power conservation) |
4 LEDs indicate -
Power On
Transmit
Receive
Input abnormal |
| Environmental: |
Temperature: 0 to 49 o C
Humidity: 0 to 85% non-condensing |
| Power: |
1. DC 10.8 - 25 VDC, 90 mA
2. AC 108-132V RMS, 0.1A |
| Shipping Weight: |
PET box - 6 lbs |
¹Note: distance depends on type of fiber and its diameter. Worst-case limit shown is for fiber with 3-db/km loss. PET 600 Series models are available to extend this distance.